Heat Recovery from Wastewater Treatment - The Best Practices

2022-04-02 08:37:52 By : Ms. Rachel Chen

We use cookies to enhance your experience. By continuing to browse this site you agree to our use of cookies. More info.

For heat recovery to be cost effective, it is essential for processes to be well coordinated and the cooling water discharge temperature needed for the process must be reached. Examples for use of cooling water from waste heat or heat exchangers: sludge drying (40 to 50 °C), hot water forward flow (40 to 60 °C), pre-heating of hot water and supply air (30 to 50 °C), and building heat forward flow (60 to 85 °C).

ΔT between waste heat source and heat sink (consumer) should be at least 5 to 10 K – the higher the better.

The recovered energy must be perfect for the process that is in use, to prevent the need for extra heat generators during peak demand.

Heat recovery can also be worthwhile in systems with low waste heat if they attain a high utilization of capacities.

It is essential for the waste heat source and heat sink to be as close to each other as possible, in order to minimize transport costs and losses.

Exact synchronization of the operating times of heat sink and the heat source ensures more efficient use of the waste heat. If demand and supply are not completely synchronous, a heat accumulator could be a good solution.

The economic benefits are higher when the system is in operation for longer and the utilization of the available capacities is higher.

The investment costs are directly affected by factors such as heat transport and storage.

If a sensitive process uses just waste heat, it may be essential to provide a backup heat generation system in case there is a failure of the waste heat source.

Air-cooled blowers, compressors or turbos with an acoustic hood are perfect for exhaust-air heating of rooms. For this purpose, the exhaust air louvre of the AERZEN unit is provided with an exhaust duct. This permits use of the cooling air for the silencer, the compressor stage and the pipe system under the acoustic hood, while the exhaust air from the oil cooler can be used for room heating. The waste heat, at a temperature of 30 to 60 °C, is concentrated through the exhaust duct and can then be guided through air ducts into the rooms that are to be heated.

Temperature-controlled flaps are employed for regulating the room temperature. The discharge-side gas flow itself proves to be more promising for heat recovery. It comprises of up to 85% of the electrical energy in the form of heat. It is possible to recover this energy by means of a compact heat exchanger, which is installed in the piping downstream from the compressor (on the discharge side).

Type reference & life cycles (operating hours).

In wastewater treatment plants, blowers, Delta Hybrid compressors and turbos that reach maximum air discharge temperatures of 140 °C are used. A condensate trap is not needed. Wastewater treatment plants are considered to be the facilities in municipalities and cities that use the most electricity. Thus, due to widespread uncertainty concerning the future global energy matrix and the resulting energy market price, there is an urgent requirement to increase energy efficiency.

By using a heat exchanger with a low differential pressure (<30 mbar) the blower station consumes just slightly more energy than normal (<2 % of the operating energy input). On the other hand, the energy saved is many times higher than the extra input power needed. Heat recovery systems for wastewater treatment plants, example, for optimal support of the sludge-drying process, are normally designed to produce the return flow of cooling water from the heat exchanger at >70 °C at the maximum heat transfer rate.

Case 1: hot water > 70 °C Case 2: increased cooling water flow Case 3: increased cooling water flow and transferred heat quantity optimized

An annual load duration curve can be used for estimating the percentage of required heat that can be achieved using a system designed for partial load operation. This example of a heating system points out that the peak capacity is required only for a few hours during the year. It is possible to cover 50 to 70 % of the heat requirement in a system designed for 15 to 25 % of the power requirement. Other applications must be analyzed individually.

Optimal waste-heat recovery needs a determination of the available heat quantity. This relies on the mass flow/volume flow, usable temperature difference, the specific thermal capacity of the heat transfer medium, and the time of availability.

Operating hours of the consumer per year

Function: compressed medium flows via the cooler’s pipes, cooling water flows through the pipes in a counterflow. The louvre design of the tubes guarantees effective heat transfer and minimal pressure loss.

Variants: Permanently installed or removable pipe bundles, ribbed or smooth pipes, stainless steel for high gas temperatures, nickel/copper for seawater.

The design tool lets you quickly find the best heat exchanger for your system!

ARN removable pipe bundle AFN fixed pipe bundle

A = cooler length (without flanges) in mm B = flange width in mm C = distance between the water connections in mm The exact dimensions will be determined during the configuration phase.

This information has been sourced, reviewed and adapted from materials provided by Aerzen Machines Ltd.

For more information on this source, please visit Aerzen Machines Ltd.

Please use one of the following formats to cite this article in your essay, paper or report:

Aerzener Maschinenfabrik GmbH. (2020, January 06). Heat Recovery from Wastewater Treatment - The Best Practices. AZoM. Retrieved on April 02, 2022 from https://www.azom.com/article.aspx?ArticleID=14864.

Aerzener Maschinenfabrik GmbH. "Heat Recovery from Wastewater Treatment - The Best Practices". AZoM. 02 April 2022. <https://www.azom.com/article.aspx?ArticleID=14864>.

Aerzener Maschinenfabrik GmbH. "Heat Recovery from Wastewater Treatment - The Best Practices". AZoM. https://www.azom.com/article.aspx?ArticleID=14864. (accessed April 02, 2022).

Aerzener Maschinenfabrik GmbH. 2020. Heat Recovery from Wastewater Treatment - The Best Practices. AZoM, viewed 02 April 2022, https://www.azom.com/article.aspx?ArticleID=14864.

Do you have a question you'd like to ask regarding this article?

AZoM spoke to Jonathan Venditti from Klüber Lubrication about the significance of lubrication in chemical processes, and how a focus on these products can contribute toward greener industrial chemistry.

AZoM speaks to Dr. Spence Macdonald from ABOzymes about his discovery of a novel biopolymer, acholetin, synthesized from a bacterial enzyme.

AZoM speaks with Dr. Rajashekar Badam from JAIST about his recently formulated method for anode fabrication that could pave the way to the very fast charging of lithium-ion batteries.

Discover ODIN, a compact deep UV Raman spectrometer by IS-Instruments.

This product profile outlines how the Carousel 12 Plus Reaction Station is used as an effective personal synthesis station.

IKA has released the new reactor system EasySyn which is the only reactor system available on the market where all components are available from a single source.

AZoM.com - An AZoNetwork Site

Owned and operated by AZoNetwork, © 2000-2022